Prod.No. 92485 EAN: 4007529924851 PD4-M-1C-C-PS-SM
- Voltage: 110 – 240 V AC 50 / 60 Hz
- Dimensions: SM= Ø 101 x 76 mm
- Power consumption: approx. 0.7 W
- Features
- Description
- Accessories
- Downloads
Features
Designation | Value |
---|---|
Voltage | 110 – 240 V AC 50 / 60 Hz |
Dimensions | SM= Ø 101 x 76 mm |
Power consumption | approx. 0.7 W |
Detection area | horizontal 360° (Ceiling mounting) |
Range |
max. 40 m x 5 m across max. 20 m x 3 m towards |
Monitored area (tangential movement) | 250 m² / 2.5 m mounting height |
Mounting height min./max./recommended | 2.4 m / 2.6 m / 2.5 m |
Degree / class of protection | SM= IP54 / Class II |
Impact strength | IK04 |
Ambient temperature | -25 °C to +50 °C |
Housing | polycarbonate, UV-resistant |
Material color | white mat, similar to RAL9010 |
Channel 1 (lighting control) | |
Switching power |
2300 W, cos φ = 1 1150 VA, cos φ = 0.5 300 W LED max. inrush current Ip (20 ms) = 120 A |
Type of contact (k) | 1x µ-contact, NO contact with tungsten pre-make contact, additional NC-safety contact |
Follow-up time | 15 sec – 30 min, Pulse |
Switch-on threshold | 10 – 2000 Lux |
Light measuring | Mixed light measuring |
Description
Occupancy detector with NO contact and safety circuit by NC contact
Guarantees illumination even if sensor fails
Designed for corridors
Version as master device
Detection area can be extended by using slave devices
Manual switching via push-button possible
Additional functions can be set up using the optional remote control.
Factory settings 10 min and 500 lux
There are markings to ensure correct alignment during installation
Application examples:
entrance halls, corridors/hallways, small offices, open-plan offices, conference rooms, classrooms/seminar rooms
Follow us: