PD4N-CAS DALI-2
Product Information
- Casambi-enabled occupancy detector
- DALI-2 interface for controlling digital dimmable ECGs in broadcast/multicast mode
- Integrated temperature monitoring and short-circuit detection
- Version as single-master device, can be networked wirelessly
- DALI output power can be increased with accessories
- Bright LED indication for commissioning
- Mixed light measurement with internal and external light sensor
- Weighting between internal and external light sensor can be adapted to suit the application
- Adjustment of the reflection factor and input of the luminosity for the display of the actual luminosity in the app
- Extension of the detection area with additional B.E.G. Casambi devices possible
- Individual adaption of detection sensitivity for each PIR sensor
- Detection area can be restricted with blinds
- Functions adjustable via Casambi app
- Including pre-assembled spring clamp with strain relief and contact protection cap for recessed ceiling mounting
- Accessory for surface mounting available
- Accessories for wall mounting optionally available
- Further accessories for colour matching optionally available
- Application examples:
entrance halls, corridors/hallways, open-plan offices, conference rooms, classrooms/seminar rooms, sports halls/ storage rooms, underground car parks, staircases, toilets, equipment rooms, small offices
COMING SOON!
Technical Data
- Voltage:
- 230 V AC ±10% 50 Hz
- Dimensions:
- Ø 106 x 95 mm
- Settings:
- Casambi App
- Power consumption:
- 0.5 W
- Detection area:
- horizontal 360° oval (Ceiling mounting)
- Range:
- max. Ø 24 m across
max. Ø 8 m towards
max. Ø 6.4 m seated - Monitored area (tangential movement):
- 450 m² / 2.5 m mounting height
- Mounting height min./max./recommended:
- 2 m / 10 m / 2.5 m
- Degree / class of protection:
- IP20 / Class II
- Impact strength:
- IK04
- Ambient temperature:
- -5 °C to +45 °C
- Housing:
- polycarbonate, UV-resistant
- Number of PIR sensors:
- 4
- Channel 1 (lighting control)
- DALI output:
- 80 mA (guaranteed), 125 mA (max.), Shut-down mechanism
- supported control gear:
- DT0. DT5. DT6. DT7. DT8
- supported control devices:
- - (single master)
- Follow-up time:
- 1 sec – 60 min
- Brightness set value:
- 1 – 4000 Lux
- Mixed light measuring
Description
Description | Colour | Part number | EAN number |
---|---|---|---|
PD4N-CAS DALI-2 | white mat, similar to RAL9010 | 93473 | 4007529934737 |