Prod.No. 93525 EAN: 4007529935253 Indoor 180-KNXs-DX covering not included
- Voltage: via KNX BUS
- Dimensions: (covering not included) 70 x 70 x 61 mm
- Typ. power input: 12 mA
- Features
- Description
- Accessories
- Downloads
Features
Designation | Value |
---|---|
Voltage | via KNX BUS |
Dimensions | (covering not included) 70 x 70 x 61 mm |
Typ. power input | 12 mA |
Detection area | horizontal 180° (Wall mounting) |
Range |
max. 10 m across max. 3 m towards |
Monitored area (tangential movement) | 150 m² / 1.1 m mounting height |
Mounting height min./max./recommended | 1 m / 2.2 m / 1.1 m |
Degree / class of protection | IP20 / Class III |
Impact strength | IK05 |
Temperature measurement range | -5 °C to +45 °C |
Ambient temperature | -25 °C to +55 °C |
Housing | polycarbonate, UV-resistant |
Number of light sensors | 1 |
Material color | - |
Number of PIR sensors | 1 |
KNX TP 256 | Yes |
Orientation light | 5 – 100 % / OFF / 1 min – 255 min |
Night light | 5 – 100 % |
Brightness set value | 5 – 2000 Lux |
Description
KNX occupancy detector with integrated KNX bus coupler, especially for installation in walls
KNX Secure ready
HCL/RGB control
Parameterisation from ETS 5 for integration into KNX systems
Individual adaption of the PIR sensor sensitivity
Mixed light measurement using internal and remote (optional) light sensors
Intelligent semi-automatic mode, occupancy-independent regulating mode (photoelectric switch), full automatic mode
1 x Light (for regulating or switching), 1 x slave output, 3 separate HVAC-blocs
Regulation of up to three lighting groups using offset (external influence possible)
Short presence, self-adjusting follow-up time, corridor function
Various locking functions
Soft-start
Two logic modules
Recall of light scenes
Deactivatable status indicators
Temperature- and noise sensor
The product database for import into the ETS database can be downloaded from the B.E.G. homepage.
Detection area can be extended thanks to master-slave-mode
Extensive optimization options for light measurement
Measured light value is communicated to the bus
Adaption of dimming curve
Bidirectionally remote control-capable with the IR adapter and the B.E.G. smartphone app
PIN code
IR remote control-capable via IR remote control (optionally)
5 button remote control, programmable at choice (accessory)
Programming button (phys. address) can be operated via remote control
HVAC mode (0=automatic, 1=comfort, 2=stand-by, 3=economy, 4=antifreeze/heat protection)
Manual influence via external KNX push buttons possible
Function control (heartbeat, cyclical sending)
Occupancy simulation
Forced switch-off
Intelligent central-off function
Premonition of switch-off
Burn-in function for fluorescent lamps selectable from 1h till 100h
Behaviour upon bus voltage return definable at choice
Variable safety pause after switching off the lights
Application examples: monitoring of public lavatories, corridors, archive rooms, conference rooms