Prod.No. 92735 EAN: 4007529927357 PD4-M-TRIO-DIM-FC
- Voltage: 110 – 240 V AC 50 / 60 Hz
- Dimensions: FC= Ø 117 x 100 mm
- Power consumption: approx. 0.6 W
- Features
- Description
- Accessories
- Downloads
Features
Designation | Value |
---|---|
Voltage | 110 – 240 V AC 50 / 60 Hz |
Dimensions | FC= Ø 117 x 100 mm |
Power consumption | approx. 0.6 W |
Detection area | horizontal 360° (Ceiling mounting) |
Range |
max. Ø 24 m across max. Ø 8 m towards max. Ø 6.4 m seated |
Monitored area (tangential movement) | 450 m² / 2.5 m mounting height |
Mounting height min./max./recommended | 2 m / 10 m / 2.5 m |
Degree / class of protection | FC= IP20 / Class II |
Impact strength | IK04 |
Ambient temperature | -25 °C to +50 °C |
Housing | polycarbonate, UV-resistant |
Material color | white mat, similar to RAL9010 |
Channel 1 and Channel 2 (lighting control) | |
Switching power |
3000 W, cos φ = 1 1500 VA, cos φ = 0.5 300 W LED max. inrush current Ip (20 ms) = 165 A max. inrush current Ip (200 µs) = 800 A |
Type of contact (k) | 1x µ-contact, NO contact with tungsten pre-make contact |
DIM output | 2 dim outputs 1-10 V DC, up to 25 ballasts per channel |
Orientation light | 20 % / OFF / ∞ |
Channel 3 (HVAC control or lighting control, potential-free (dry)) | |
Switching power |
3000 W, cos φ = 1 1500 VA, cos φ = 0.5 300 W LED max. inrush current Ip (20ms) = 165 A, (200 µs) = 800 A |
Type of contact | 1x µ-contact, dry NO contact with tungsten pre-make contact |
Channel 1 to channel 3 | |
Follow-up time | 1 min – 60 min |
Brightness set value | 10 – 2000 Lux |
Light measuring | Mixed light measuring |
Description
Occupancy detector for two separate lighting groups, for daylight-dependent lighting control
One potential-free switching channel for control of equipment (HVAC) or lighting
One common detection area
Two independent, movable light sensors
Manual switching and dimming via push button possible
Orientation light function
Relay with tungsten pre-make contact, optimised for LED loads
Version as master device
Detection area can be extended by using slave devices
Two 1-10 V interfaces for control of dimmable electronic ballasts
Additional functions can be set up using the optional remote control.
Avoidance of standby losses of the lighting system in accordance with EnEV DIN V 18599-4
Application examples:
open-plan offices, conference rooms, classrooms/seminar rooms
Follow us: