The gateway connects the KNX BUS with the DALI BUS (DALI BUS for controlling the illumination) Each gateway is for controlling and dimming up to 64 electronic ballasts in 16 groups Scenes module for controlling individual electronic ballasts RGB and TW (DT8) support Support of B.E.G. DALI-LINK multisensors, push-button modules, push-buttons and DALI relay modules Commissioning via DCA Broadcast command via integrated operating buttons Support for DALI emergency luminaires Compatible with most DALI drivers or DALI ballasts Voltage: 230 V AC -15/+10% 50 / 60 Hz Dimensions: 90 x 72 x 64 mm (4 TE) typ. power input: 5.5 mA (KNX, typical) Output voltage: 16 V DC (DALI, typical) Power consumption: 0.9 - 6 W Degree / class of protection: IP20 / Class II Ambient temperature: -5 °C to +45 °C Housing: PA66 Material color: - KNX TP 256: Yes Nominal current: 160 mA Nominal current (max.): 210 mA Manufacturer: B.E.G. Brück Electronic GmbH Description: DA64-230/KNX REG Material color: - Item number: 93302 -