1-channel occupancy detector with two simultaneously operating relay outputs, which enable distribution to different phases The switching channel with the two relay outputs closes when the operating voltage of the detector fails, so the lighting remains on as long as the two phases of the luminaires are supplied with power. The device requires an operating voltage. The third phase can be used for this purpose. Designed for corridors Version as master device Detection area can be extended by using slave devices Manual switching via push-button possible Additional functions can be set up using the optional remote control. There are markings to ensure correct alignment during installation Voltage: 110 - 240 V AC 50 / 60 Hz Dimensions: FC= Ø 117 x 100 mm Power consumption: approx. 0.5 W Detection area: horizontal 360° (Ceiling mounting) Range: max. 40 m x 5 m across, max. 20 m x 3 m towards Monitored area (tangential movement): 250 m² / 2.5 m mounting height Mounting height min./max./recommended: 2.4 m / 2.6 m / 2.5 m Degree / class of protection: FC= IP20 / Class II Impact strength: IK04 Ambient temperature: -25 °C to +50 °C Housing: polycarbonate, UV-resistant Material color: white mat, similar to RAL9010 Channel 1 (lighting control, potential-free (dry)) Switching power: 2300 W, cos φ = 1, 1150 VA, cos φ = 0.5 , 300 W LED Type of contact: 2x µ-contact, dry Contact NC with tungsten pre-make contact Follow-up time: 15 sec - 30 min, Pulse Switch-on threshold: 10 - 2000 Lux Mixed light measuring Manufacturer: B.E.G. Brück Electronic GmbH Description: PD4-M-TRIO-C-3P-FC Material color: white mat, similar to RAL9010 Item number: 92746 -