Occupancy detector with NO contact and safety circuit by NC contact Guarantees illumination even if sensor fails Designed for corridors Version as master device Detection area can be extended by using slave devices Manual switching via push-button possible Additional functions can be set up using the optional remote control. Factory settings 10 min and 500 lux There are markings to ensure correct alignment during installation Voltage: 110 - 240 V AC 50 / 60 Hz Dimensions: Ø 101 x 76 mm Power consumption: approx. 0.7 W Detection area: horizontal 360° (Ceiling mounting) Range: max. Ø 40 m across, max. Ø 20 m towards Monitored area (tangential movement): 250 m² / 2.5 m mounting height Mounting height min./max./recommended: 2.4 m / 2.6 m / 2.5 m Degree / class of protection: IP54 / Class II Impact resistance level: IK04 Ambient temperature: -25 °C to +50 °C Housing: polycarbonate, UV-resistant Material color: white mat, similar to RAL9010 Channel 1 (lighting control) Switching power: 2300 W, cos φ = 1, 1150 VA, cos φ = 0.5 , 800 W LED, max. inrush current Ip (20 ms) = 120 A Type of contact: 1x µ-contact, NO contact with tungsten pre-make contact, additional NC-safety contact Follow-up time: 15 sec - 30 min, Pulse Switch-on threshold: 10 - 2000 Lux Mixed light measuring Manufacturer: B.E.G. Brück Electronic GmbH Description: PD4-M-1C-C-PS-SM Material color: white mat, similar to RAL9010 Item number: 92485 -