Occupancy detector designed for corridors One channel for light switching One additional potential-free (dry) contact for HVAC Version as master device Detection area can be extended by using slave devices Manual switching via push-button possible Alarm pulse: the detector triggers only when three movements are detected within 9 seconds Additional functions can be set up using the optional remote control. There are markings to ensure correct alignment during installation Factory settings 10 min and 500 lux (15 min HVAC) Voltage: 110 - 240 V AC 50 / 60 Hz Dimensions: Ø 101 x 76 mm Power consumption: < 0.5 W Detection area: horizontal 360° (Ceiling mounting) Range: max. Ø 40 m across, max. Ø 20 m towards Monitored area (tangential movement): 250 m² / 2.5 m mounting height Mounting height min./max./recommended: 2.4 m / 2.6 m / 2.5 m Degree / class of protection: IP54 / Class II Impact resistance level: IK04 Ambient temperature: -25 °C to +50 °C Housing: polycarbonate, UV-resistant Material color: white mat, similar to RAL9010 Channel 1 (lighting control) Switching power: 2300 W, cos φ = 1, 1150 VA, cos φ = 0.5 , 800 W LED, max. inrush current Ip (20 ms) = 165 A, max. inrush current Ip (200 µs) = 800 A Type of contact: 1x µ-contact, NO contact with tungsten pre-make contact Follow-up time: 15 sec - 30 min, Pulse Switch-on threshold: 10 - 2000 Lux Channel 2 (HVAC control potential-free (dry)) Switching power: 3 A (230 V), cos φ = 1 Type of contact: 1x µ-contact, dry NO contact Follow-up time: 5 min - 120 min, Alarm pulse, Pulse Mixed light measuring Manufacturer: B.E.G. Brück Electronic GmbH Description: PD4-M-2C-C-SM Material color: white mat, similar to RAL9010 Item number: 92440 -