PD4-M-DIM-HKL-16A
Product Information
- Occupancy detector for daylight-dependent lighting control
- 1 – 10 V interface for controlling analog, dimmable ballasts
- Additional switching channel for the following function:
Cut-Off (complete ECG switch-off to avoid standby losses). - One additional potential-free (dry) contact for HVAC
- Manual switching and dimming via push button possible
- Orientation light function
- Version as master device
- Detection area can be extended by using slave devices
- Additional functions can be set up using the optional remote control.
- Relay with tungsten pre-make contact, optimised for LED loads
- Avoidance of standby losses of the lighting system in accordance with EnEV DIN V 18599-4
- Application examples:
open-plan offices, conference rooms, classrooms/seminar rooms, entrance halls, corridors/hallways, staircases, toilets, equipment rooms, small offices
Product no longer available
Technical Data
- Voltage:
- 110 – 240 V AC 50 / 60 Hz
- Dimensions:
- FC= Ø 97 x 103 mm
- Power consumption:
- approx. 0,6 W
- Detection area:
- horizontal 360° (Ceiling mounting)
- Range:
- max. Ø 24 m across
max. Ø 8 m towards
max. Ø 6,4 m seated - Monitored area (tangential movement):
- 450 m² / 2,5 m mounting height
- Mounting height min./max./recommended:
- 2 m / 10 m / 2,5 m
- Degree / class of protection:
- FC= IP20 / Class II
- Impact strength:
- IK04
- Ambient temperature:
- -25 °C to +50 °C
- Housing:
- polycarbonate, UV-resistant
- Channel 1 (lighting control)
- Switching power:
- 2300 W, cos φ = 1
1150 VA, cos φ = 0,5
300 W LED
max. inrush current Ip (20 ms) = 165 A
max. inrush current Ip (200 µs) = 800 A - Type of contact:
- 1x µ-contact, NO contact with tungsten pre-make contact
- DIM output:
- 1 – 10 V DC, up to 50 ballasts
- Follow-up time:
- 1 min – 30 min
- Brightness set value:
- 10 – 2000 Lux
- Channel 2 (HVAC control potential-free (dry))
- Switching power:
- PD4-M-DIM-HVAC-3A-FC: 3 A, 230 V, cos φ = 1
PD4-M-DIM-HVAC-16A-FC: 16 A, 230 V, cos φ = 1 - Type of contact:
- dry NO contact
- Follow-up time:
- 5 min – 120 min, Alarm pulse, Pulse
- Mixed light measuring
Description
Description | Colour | Part number | EAN number |
---|---|---|---|
PD4-M-DIM-HVAC-16A-FC | white mat, similar to RAL9010 | 92547 | 4007529925476 |