PD2-M-2C-12-48V-RR

Product Information

  • Occupancy detector with operating voltage of 12-48 V
  • Two potential-free (dry) channels
  • For channel 1, output of brightness-dependent resistance value also available, for additional analogue connection
  • Can be used as either Master device or Slave device
  • Manual switching via push-button possible
  • Additional functions can be set up using the optional remote control.
  • Factory settings 10 min and 500 lux (15 min HVAC)
  • Application examples: offices, schools, nursery schools, hospitals, conference rooms.
Voltage:
12 – 48 V AC / DC
Dimensions:
SM= Ø 98 x 47 mm
FC= Ø 80 x 85 mm
Power consumption:
< 1 W
Detection area:
vertical 360°
Range:
max. Ø 10 m across
max. Ø 6 m towards
max. Ø 4 m seated
Monitored area (tangential movement):
78 m² / 2,5 m mounting height
Mounting height min./max./recommended:
2 m / 5 m / 2,5 m
Degree / class of protection:
SM= IP20 / Class II
FC= IP20 / Class II
Ambient temperature:
-25 °C to +50 °C
Housing:
Polycarbonate, UV-resistant
Channel 1 (lighting control, potential-free (dry))
Switching power:
0,1 A; cos φ = 1 with Reed relay
Type of contact:
1x µ-contact, dry NO contact
Follow-up time:
15 sec – 30 min, Pulse
Brightness set value:
10 – 2000 Lux
Channel 2 (HVAC control potential-free (dry))
Switching power:
0,1 A; cos φ = 1 with Reed relay
Type of contact:
1x µ-contact, dry NO contact
Follow-up time:
5 min – 120 min, Alarm pulse, Pulse
Mixed light measuring
Description Colour Part number EAN number
PD2-M-2C-12-48V-RR-SM white mat, similar to RAL9010 92305 4007529923052
PD2-M-2C-12-48V-RR-FC white mat, similar to RAL9010 92306 4007529923069
Generate Data sheet

Local advice

Our office is always at your side for advice and action. For questions on ordering, products, technology or planning, just contact us:

Telefon: +49 2266 901 210
E-Mail: info(@)beg(.)de
Contact form