Prod.No. 92167 EAN: 4007529921676 PD2-M-DIM-FC
- Voltage: 110 – 240 V AC 50 / 60 Hz
- Dimensions: FC= Ø 80 x 85 mm
- Power consumption: approx. 0.5 W
- Features
- Description
- Accessories
- Downloads
Features
Designation | Value |
---|---|
Voltage | 110 – 240 V AC 50 / 60 Hz |
Dimensions | FC= Ø 80 x 85 mm |
Power consumption | approx. 0.5 W |
Detection area | horizontal 360° (Ceiling mounting) |
Range |
max. Ø 10 m across max. Ø 6 m towards max. Ø 4 m seated |
Monitored area (tangential movement) | 78 m² / 2.5 m mounting height |
Mounting height min./max./recommended | 2 m / 5 m / 2.5 m |
Degree / class of protection | FC= IP20 / Class II |
Impact strength | IK05 |
Ambient temperature | -25 °C to +50 °C |
Housing | polycarbonate, UV-resistant |
Material color | white mat, similar to RAL9010 |
Channel 1 (lighting control) | |
Switching power |
2300 W, cos φ = 1 1150 VA, cos φ = 0.5 300 W LED, minimum runtime > 5 min max. inrush current Ip (20 ms) = 165 A max. inrush current Ip (200 µs) = 800 A |
Type of contact (k) | 1x µ-contact, NO contact with tungsten pre-make contact |
DIM output | 1-10 V DC, up to 50 ballasts |
Follow-up time | 1 min – 30 min |
Brightness set value | 10 – 2000 Lux |
Light measuring | Mixed light measuring |
Description
Occupancy detector for daylight-dependent lighting control
1 – 10 V interface for controlling analog, dimmable ballasts
Additional switching channel for the following function:
Cut-Off (complete ECG switch-off to avoid standby losses).
Orientation light function
Manual switching and dimming via push button possible
Version as master device
Detection area can be extended by using slave devices
Additional functions can be set up using the optional remote control.
Relay with tungsten pre-make contact, optimised for LED loads
Avoidance of standby losses of the lighting system in accordance with EnEV DIN V 18599-4
Application examples:
entrance halls, small offices, corridors/hallways, open-plan offices, conference rooms, classrooms/seminar rooms