PD9-M-DIM-HVAC

Product Information

    Discontinued product

  • Mini occupancy detector for light switching with additional potential-free (dry) contact
  • 1 – 10 V interface for controlling analog, dimmable ballasts
  • Orientation light function
  • Additional switching channel for the following function:
    Cut-Off (complete ECG switch-off to avoid standby losses).
  • One additional potential-free (dry) contact for HVAC
  • Manual switching and dimming via push button possible
  • Easy operation with remote control (required)
  • Version as master device
  • Detection area can be extended with slave devices
  • Relay with tungsten pre-make contact, optimised for LED loads
  • Power supply passes through the hole in the ceiling for the detector (34 mm Ø)
  • Avoidance of standby losses of the lighting system in accordance with EnEV DIN V 18599-4
  • Spring clips for quick and easy installation in suspended ceilings and light fittings
  • Includes 45 mm cover ring and blinds
  • Factory settings 5 min and 300 lux (15 min HVAC)
  • Application examples:
    entrance halls, small offices, corridors/hallways, sports halls/ storage rooms
Voltage:
110 – 240 V AC 50 / 60 Hz
Dimensions:
Sensor head: Ø 45 x 28 mm, Power supply: 165 x 24 x 24 mm
Power consumption:
approx. 0,8 W
Detection area:
horizontal 360° (Ceiling mounting)
Range:
max. Ø 10 m across
max. Ø 6 m towards
max. Ø 4 m seated
Monitored area (tangential movement):
78 m² / 2,5 m mounting height
Mounting height min./max./recommended:
2 m / 5 m / 2,5 m
Degree / class of protection:
IP20 / Class II
Impact strength:
IK03
Ambient temperature:
-25 °C to +50 °C
Housing:
polycarbonate, UV-resistant
Cable length:
45 cm, screened
Channel 1 (lighting control)
Switching power:
2300 W, cos φ = 1
1150 VA, cos φ = 0,5
300 W LED
max. inrush current Ip (20 ms) = 165 A
max. inrush current Ip (200 µs) = 800 A
Type of contact:
1x µ-contact, NO contact with tungsten pre-make contact
DIM output:
1-10 V DC, up to 50 ballasts
Follow-up time:
1 min – 30 min
Brightness set value:
10 – 2000 Lux
Channel 2 (HVAC control potential-free (dry))
Switching power:
3 A (230 V), cos φ = 1
Type of contact:
µ-contact, dry NO contact
Follow-up time:
5 min – 60 min, Pulse
Mixed light measuring
Description Colour Part number EAN number
PD9-M-DIM-HVAC-FC white mat, similar to RAL9010 92973 4007529929733
Generate Data sheet